Electrical Power Quality Experiments
Timothy L. Skvarenina Purdue University, West Lafayette, IN
Abstract This paper describes several experiments that can be performed with a second generation power harmonics analyzer, such as the Fluke 43, or with an oscilloscope. Two of the experiments described herein involve transient phenomena, while the third demonstrates the capabilities of inexpensive UPS devices.
Introduction Power quality problems may arise due to a variety of phenomena that occur on time scales ranging from less than a millisecond to steady-state. Each of these phenomenon cause different effects in the power system and require different solutions to avoid problems. A previous paper1 demonstrated several power quality experiments that could be performed with a first generation power harmonics analyzer, such as the Fluke 41. Those experiments concentrated primarily on harmonics. This paper describes several additional experiments that can be performed with a second generation power harmonics analyzer, such as the Fluke 43, or with an oscilloscope. Two of the experiments described herein involve transient phenomena, while the third demonstrates the capabilities of inexpensive UPS devices. The emphasis on these experiments was to keep the cost relatively low and to provide the student with a good demonstration of the applicable phenomena. The paper will show typical lab setups, procedures, and results.
Induction motor starting current and system voltage drop The first experiment demonstrates the starting current and system voltage drop of a three-phase induction motor. Figure 1 illustrates the set-up for this experiment. Two power sources are provided for the induction motor. The first is the three-phase supply from the bench (stiff source), while the second places a three-phase transformer between the bench supply and the motor (weak source). The stiff source is rated substantially higher than the motor, while the weak source is rated only slightly higher than the motor. By using the transformer, the effect of starting a large motor in a plant is obtained.
The first part of this experiment is the observation of the starting current of the motor. It is well known that induction motors draw six to eight times rated current when starting2. Furthermore, the duration of the starting current is affected both by the load on the motor and by the voltage that is applied to the motor. The load for the motor consisted of a DC generator that could be connected to the shaft of the motor as shown in Figure 1. A resistive load allows the generator load to be varied. The generator and resistive load were set to provide somewhat above rated motor load at normal operating speed. Of course the output of the generator is a function of
Proceedings of the 2002 American Society for Engineering Education Annual Conference and Exposition Copyright © 2002, American Society for Engineering Education
Main Menu
Skvarenina, T. (2002, June), Electrical Power Quality Experiments Paper presented at 2002 Annual Conference, Montreal, Canada. 10.18260/1-2--11343
ASEE holds the copyright on this document. It may be read by the public free of charge. Authors may archive their work on personal websites or in institutional repositories with the following citation: © 2002 American Society for Engineering Education. Other scholars may excerpt or quote from these materials with the same citation. When excerpting or quoting from Conference Proceedings, authors should, in addition to noting the ASEE copyright, list all the original authors and their institutions and name the host city of the conference. - Last updated April 1, 2015